Three phase power measurement using two wattmeter method
AIM:
To measure the power in 3 -phase balanced star connected load and to determine the power factor.
APPARATUS REQUIRED:
- Wattmeter 2.50 A, 600V 2 No’s
 - Ammeter 0 – 2.5 A M/I Type 1 No’s
 - Voltmeter 0 – 500 V M/I type 1No’s
 - Lamp load
 - Connecting wires.
 
THEORY:
The following methods are used for the measurement of three phase power.
- One Wattmeter Method : For balanced Load
 - Two Wattmeter Method : For balanced Load / Unbalance Load
 - Three Wattmeter Method : For balanced Load / Unbalance Load
 
PROCEDURE:
- Connect the circuit as shown in the Figure to measure the power in star connected load.
 - Check the circuit and switch on 3Φ supply switch.
 - Take the readings of the ammeters, voltmeters and wattmeter’s connected in the circuit.
 - Total power measured is given by (w1 + w2) watts.
 - Calculate the power by formula P = √3VLILcosΦ
 - Compare the two results.
 - Repeat the experiment for different loads
 
CIRCUIT DIAGRAM :
OBSERVATION TABLE:
Lamp load per phase  | IL ( A)  | VL (V)  | W1 (Watts)  | W2 (Watts)  | P= W1 + W2  | Φ=tan-1 {√3(w2 – w1)] /(w2 + w1)} | Power factor =Cos Φ | P = √3VLILcos Φ | |
| Star Connection | |||||||||
FORMULA USED:
- Real power,P = w1 + w2
 - Reactive power,Q = √3 (w1 – w2 )
 - Tan Φ = √3 (w1 – w2 )/ (w1 + w2)
 - Power factor = cosΦ
 
RESULT:
Thus the power in 3 -phase balanced star connected load is measured and determined the power factor