Polarity and Transformation Ratio Test on Single Phase Transformer
POLARITY & TRANSFORMATION RATIO TEST ON SINGLE PHASE TRANSFORMER
AIM:
To check the polarity of single phase transformer & find the transformation ratio.
APPARATOUS REQUIRED:
S.No. | Apparatus | Range | Type | Quantity |
1 | Ammeter | |||
2 | Voltmeter | |||
3 | Rheostats | |||
4 | SPST Switch | |||
5 | Tachometer |
MACHINES DETAILS:
THEORY :
Transformation Test
The transformation ratio ‘K’ is equal to the number of turns in the secondary divided by the number of turns in the primary OR it is the ratio of induced emf in the secondary to induced emf in the primary.
ie, K=N2/N1 =E2/E1
Polarity Test
In a transformer one terminal of primary side is positive with respect to other at every instant. for the secondary side also one terminal of primary side is positive with respect to other at every instant. If the polarity of terminals is not marked, polarity test is performed to determine the terminals which have some instant polarity. The polarity of the transformer winding is important for practical operation.
The voltmeter reads V1+V2 , The transformer is said to posses additive polarity. The voltmeter reads V1-V2 , The transformer is said to posses substractive polarity.
PRECAUTIONS:
PROCEDURE:
- Connections are made as per the circuit diagram.
- Auto transformer is kept in minimum position & supply is given.
- Vary the auto transformer & take different readings till it exceeds the rated value of voltage 110V.
- Note the voltmeter reading V1,V2& V3. If V3=V1+V2, then it is additive polarity otherwise it is subtractive polarity.
- Bring the auto transformer to minimum position & switch off the supply.
CIRCUIT DIAGRAM
ADDITIVE POLARITY
SUBSTRACTIVE POLARITY
TRANSFORMATION RATIO TEST
TABULAR COLUMN:
Additive polarity
Sl no. | V1 | V2 | V3 |
Substractive polarity
Sl no. | V1 | V2 | V3 |
Transformation ratio test
Sl no. | V1 | V2 | K=V2/V1 |
Recent Comments